Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM07284
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/24/2021 | IMONSHI1 | ENGINEERING | REVIEW | Passed | |
| 09/24/2021 | IMONSHI1 | ZONING | REVIEW | Approved | |
| 10/05/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/27/2021 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Owner to provide TFD a sprinkler annalysis for the racks. Need to higher either a FPE or Fire sprinkler designer to do the annaylsis.Plans show EH1 Density that has is .3 and the 5.6 K-Factor will not work. Building has standard response heads installed so you will also need to show that the fire sprinkler system can support the new factors. Plans also need to be submitted to TFD for a permit for high piled storage. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/27/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |