Permit Number: T21CM07284
Parcel: 13824093E

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM07284
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/24/2021 IMONSHI1 ENGINEERING REVIEW Passed
09/24/2021 IMONSHI1 ZONING REVIEW Approved
10/05/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/27/2021 JPEELDA1 FIRE REVIEW Reqs Change Owner to provide TFD a sprinkler annalysis for the racks. Need to higher either a FPE or Fire sprinkler designer to do the annaylsis.Plans show EH1 Density that has is .3 and the 5.6 K-Factor will not work. Building has standard response heads installed so you will also need to show that the fire sprinkler system can support the new factors. Plans also need to be submitted to TFD for a permit for high piled storage.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033

Final Status

Task End Date Reviewer's Name Type of Review Description
10/27/2021 NGARCIA3 OUT TO CUSTOMER Completed