Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM07277
Parcel: 13733909A

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM07277
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments and provide a written response.

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.

2. Include an electrical site plan.

3. If the tent has open sides, provide compliance with the Tucson/Pima County Outdoor Lighting Code. See section 104 for plan submittal requirements.

Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements

Final Status

Task End Date Reviewer's Name Type of Review Description
10/07/2021 VVERA1 OUT TO CUSTOMER Completed