Permit Number: T21CM07275
Parcel: 10409218A

Address:
4151 N ORACLE RD

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM07275
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments and provide a written response.

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.

2. Include an electrical site plan.

3. If the tent has open sides, provide compliance with the Tucson/Pima County Outdoor Lighting Code. See section 104 for plan submittal requirements.

Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements

Final Status

Task End Date Reviewer's Name Type of Review Description
10/07/2021 VVERA1 OUT TO CUSTOMER Completed