Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/23/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/27/2021 JPEELDA1 FIRE REVIEW Approved
09/28/2021 STEVE SHIELDS ZONING REVIEW Passed
10/05/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments and provide a written response.

Ref; Exterior Lighting.

The Outdoor Lighting calculations and electrical site plan do not provide enough information to verify compliance with the Outdoor Lighting Code (OLC) section 401.3 for “Light Trespass” into adjacent residential property. See OLC section 401.3, 401.3.1, 403.3.2, 401.3.3.

Verify that the exterior luminaire lamp color output temperature does not exceed 3500K. OLC section 402.1.

REF; 2018 IBC 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements , Tucson/Pima County Outdoor Lighting Code.
10/05/2021 LOREN MAKUS ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/05/2021 NGARCIA3 OUT TO CUSTOMER Completed