Permit Number: T21CM07264
Parcel: 12709011M

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM07264
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC unit. Reference: Section C403.1.1 and C502.2.3, IECC 2018.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/06/2021 NGARCIA3 OUT TO CUSTOMER Completed