Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM07253
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/14/2021 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Plans shall show the exiting plans Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 |
| 09/16/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide roof drainage calculations and plans. Provide overflow protection for the roof. Reference: Sections 1101, 1106 and 1108, IPC 2018. |
| 09/16/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Demonstrate energy code compliance for the addition to the building envelope using calculations based on the 2018 International Energy Conservation Code. Reference: Section C502.1, International Energy Conservation Code 2018. 2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC unit. Reference: Section C403.1.1 and C502.2.3, IECC 2018. 3. Provide calculations to verify that adequate ventilation will be provided for the occupied addition. Reference: Section 403.3.1.1, IMC 2018. |
| 09/16/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/22/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1; Code Review: Do Buildings A and B have separate tenants or companies and separate addresses/suite numbers/building numbers? This would require each building to have a separate Certificate of Occupancy. Please verify. 2. Sheet A1; Code Study: The areas of Buildings A, B, and C are listed together in the Code Study. The occupant load indicated is for the combination of those three separate buildings and for the new addition. If there are currently separate Certificates of Occupancy for each building, the new addition SF and occupant load must be assigned to either Building A or Building B. Please verify and indicate on this sheet. 3. Sheets A1 through A6: The architect of record must indicate on his seal the date this seal was signed. 4. General: Please provide written responses to all review comments. |
| 09/27/2021 | SSHIELD1 | ENGINEERING | REVIEW | Reqs Change | See Zoning comments |
| 09/27/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM07253 2424 E Speedway Blvd. – O-3 Office Addition (1st Review) TRANSMITTAL: September 27, 2021 This site is located in O-3 Zone (4.7.15) Administrative and Professional Office is an allowed use in the zone (Table 4.8-3), subject to Use Specific Standard 4.9.13.K. 1. Per Unified Development Code (UDC) Article 3.3.3.G.2.c a site (development package) is required as you are adding additional building square footage. Development Package (DP) meeting the requirements of Administrative Manual (AM) Section 2-06 must be submitted and approved prior to approval of the building plan. The AM can be found at: https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-8283. The DP is a separate submittal and shall be submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using the “Submission Type” “Site Review”. The DP will need to be approved prior to approval of this plan. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. |
| 09/27/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 10/06/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments and provide a written response. The electrical line diagram shows 3 #12 branch circuit conductors installed for the new electrical devices and Mini Split AC unit, 3 branch circuits total required.. Per 2017 NEC arts 210 , 240, and 310 the required number of conductors required to provide for 3 - 20 amp, 110 volt branch circuits is 5 # 12, not 3. 3- ungrounded, 2- grounded (min), and 1 grounding conductor. Please revise the electrical drawing to show the correct number of conductors and re- submit. REF; 2018 IBC 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements , Tucson/Pima County Outdoor Lighting Code. |