Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM07230
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/02/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/02/2021 | SBLOOD1 | ENGINEERING | REVIEW | Approved | |
| 11/03/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments and provide a written response. 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional. 2. It appears that all 4 A, B, C, D, PV array outputs are connecting to the same electrical service equipment. Provide a complete electrical line diagrams showing how all 4 systems are interconnected. Ref; 2018 IBC section 107.1.2, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |