Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM07229
Parcel: 11107146C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM07229
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/02/2021 SBLOOD1 ENGINEERING REVIEW Approved
11/03/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments and provide a written response.

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional.

2. It appears that all 4 A, B, C, D, PV array outputs are connecting to the same electrical service equipment. Provide a complete electrical line diagrams showing how all 4 systems are interconnected.

Ref; 2018 IBC section 107.1.2, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements