Permit Number: T21CM07229
Parcel: 11107146C

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM07229
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2021 JVINCEN1 FIRE REVIEW Approved
09/24/2021 STEVE SHIELDS ZONING REVIEW Approved
09/30/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Please provide.
2. General: Please provide structural calculations investigating the adequacy of the existing roof structure to support the new PV loads. These calculations must be prepared, sealed, signed, and dated by a registered design professional.
10/19/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.)
Only one floodplain use permit will be needed for all four solar permits: T21CM07229, T21CM07230, T21CM07231, and T21CM07232. For description make sure to say floodplain use permit and reference all four solar permit numbers. And don't forget to include the total cost estimate for all four installs.
Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Instructions:
1. Is this for a new or existing activity application? - Please select New Application.

2. Submission Type - Select Floodplain Use Permit.

3. Project Name - Enter a name for your project.

4. Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided.

5. Type of Permit - Select Commercial or Residential (Residential is for work on single family residences and duplexes.)

6. Complete the Applicant Info. (Note APA# is for applicants with an advance payment account. Leave blank is you do not have an APA account.

7. Complete the Contractor, Owner and Architect/Engineer sections as applicable.

8. Supporting Documentation Upload - Provide a complete cost estimate for the project. You may also provide additional documents you think will be helpful.

9. Sign the application and submit.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
10/19/2021 VVERA1 OUT TO CUSTOMER Completed