Permit Number: T21CM07224
Parcel: 137100840

Address:
5409 S ALASKA DR

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM07224
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM07224
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. All construction drawings submitted after June 1, 2010 for one- or two-family dwellings must provide gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. When the clothes washer is not near an exterior wall show a gray water bathing fixture drain looped 3’ beyond an exterior wall below grade before connection to the building drain. Add the appropriate detail found at the web site: https://www.tucsonaz.gov/pdsd/water-energy-conservation

FLOOR PLANS:

1. Show a maximum ½” floor elevation changes at a notated accessible route entrance on the floor plan, R106.1.1. Update the 1-1/2” notation on the Proposed Plan sheet A-2.

PLUMBING PLANS:

1. Show horizontal branch drainpipes sized with acceptable number of fixture units, Table P3005.4.1. (max 6 units on 2” pipe size). Update the building drain from 2” to 3” on sheet P-1.

ELECTRICAL PLANS:

1. Revise the electrical load calculations following Table E3602.2 for sizing the general usage loads. Add the total nameplate for the air conditioning units as continuous loads.
2. Show the Electric Vehicle Supply Equipment 40 ampere 240 volt dedicated branch circuit “EV Ready” on the panel schedule, N1104.2.1. Include the Electric Vehicle load entry (typically 7680 watts) in the electrical load calculations (continuous demand) like the HVAC entry, N1104.2.2.