Permit Number: T21CM07209
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM07209
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T21CM07209

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Conditionally Approved
e001 electrical notes, symbols & abbreviations: No electrical issues
ed101 electrical demolition plans: No electrical issues
ep101 new electrical plans: No electrical issues
ep601 panel schedules: No electrical issues
ep701 partial single line diagram & partial fire alarm diagram: Panel P2LG is called out as existing, but is New per ep601.
Need to clarify for electrical contractor/bid purpose.

PLUMBING REVIEW COMMENTS:
Approved
09/14/2021 JPEELDA1 FIRE REVIEW Approved
09/22/2021 STEVE SHIELDS ZONING REVIEW Approved
09/22/2021 SSHIELD1 ENGINEERING REVIEW Passed
09/22/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/04/2021 ROBERT SHERRY WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/04/2021 NGARCIA3 OUT TO CUSTOMER Completed