Permit Number: T21CM07192
Parcel: 10510010D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM07192
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2021 JPEELDA1 FIRE REVIEW Approved
09/16/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/16/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/16/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/16/2021 ROBERT SHERRY WATER REVIEW Completed
09/21/2021 IMONSHI1 ZONING REVIEW Approved
09/21/2021 IMONSHI1 ENGINEERING REVIEW Passed
09/21/2021 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
10/05/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical comments and provide a written response.
1. Sign and date the lighting Comcheck. 2. Provide GFI protection for the receptacles within 6' of a sink. 3. Correlate the power requirements for the water heater with the plumbing specifications. See plumbing plan.
Ref; 2018 IBC section 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal Requirements.