Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM07192
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/13/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
09/16/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/16/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
09/16/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
09/16/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
09/21/2021 | IMONSHI1 | ZONING | REVIEW | Approved | |
09/21/2021 | IMONSHI1 | ENGINEERING | REVIEW | Passed | |
09/21/2021 | IMONSHI1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
10/05/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical comments and provide a written response. 1. Sign and date the lighting Comcheck. 2. Provide GFI protection for the receptacles within 6' of a sink. 3. Correlate the power requirements for the water heater with the plumbing specifications. See plumbing plan. Ref; 2018 IBC section 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal Requirements. |