Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM07190
Parcel: 10510010D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM07190
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2021 JPEELDA1 FIRE REVIEW Approved
09/16/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/16/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/16/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/16/2021 ROBERT SHERRY WATER REVIEW Completed
09/21/2021 IMONSHI1 ZONING REVIEW Approved
09/21/2021 IMONSHI1 ENGINEERING REVIEW Passed
09/21/2021 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
10/05/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved