The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T21CM07188
Parcel: 13408278A

Address:
8485 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM07188
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Completed
11/03/2021 JVINCEN1 FIRE REVIEW Approved
11/04/2021 ROBERT SHERRY WATER REVIEW Reqs Change Comment not addressed. [Initial comment: Show the location of the water meter, backflow preventer, and the water service pipe on a site plan. Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1 and 107.2.6, IBC 2018.]