Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T21CM07188
Parcel: 13408278A

Address:
8485 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM07188
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM07188

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. The information in the code data box on sheet G21 does not match the information on the cover page. The square footages do not match. It also states that this is a new building.
2. The code data box states that there is an educational occupancy. Provide clarification or correct drawings to properly correlate.
3. The code data box states that this is a nonseparated mix use building however, it states that the Table 508.4 is referenced. This table only applies to separated mix use buildings.
4. The travel distances must be calculated all the way to a protected exit. It appears that the travel distances for the second floor end at the stairs. If that stair shaft is a protected exit, the travel leaves the stair shaft enters an unprotected are and then to exit discharge. Either correct the unprotected exit or show the travel distance all the way to the exit.
5. Provide complete drawings for the elevator. Provide all related details and shaft sections.

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Denied
1. If any new water lines are being installed provide a new water line and new sewer lines drawing.
09/22/2021 SSHIELD1 ENGINEERING REVIEW Passed
09/22/2021 STEVE SHIELDS ZONING REVIEW Approved
09/22/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/24/2021 JVINCEN1 FIRE REVIEW Reqs Change See building comments. Make corrections, provide written response.
09/30/2021 ROBERT SHERRY WATER REVIEW Reqs Change Show the location of the water meter, backflow preventer, and the water service pipe on a site plan. Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1 and 107.2.6, IBC 2018.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/01/2021 VVERA1 OUT TO CUSTOMER Completed