Permit Number: T21CM07158
Parcel: 12413008A

Address:
925 E MILL ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM07158
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2022 LSHAMIS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
09/09/2021 JPEELDA1 FIRE REVIEW Approved
09/14/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Per the 2018 IBC Section 107 and the City of Tucson, construction documents shall be prepared by a registered design professional. Documents shall include a site plan and Code Analysis including requirements for egress, accessibility, plumbing fixtures, fire protection, and exiting per Chapters 7 and 8 of the 2018 IEBC.
09/15/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
09/15/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
09/15/2021 ROBERT SHERRY WATER REVIEW Reqs Change Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
09/21/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM07158
925 E Mill St – I-1
TI Office

TRANSMITTAL: September 21, 2021
This site is located in the I-1 zone (UDC 4.7.29), Administrative Office is an allowed use in the zone, subject to Use Specific Standard 4.9.13.Q.

1. As it appears that you are proposing a change of use from warehouse (commercial storage) to office you will need to do one of the following: 1) Provide a approved C of O for a use that parks at a ratio of 1 space per 300 sq. ft. of gross floor area or more intense, 2) Demonstrate that the required vehicle parking for the office use is provided on site, or 3) demonstrate that you meet the requirements of UDC Article 3.3.3.H and provide a copy of a lease with the verbiage required in UDC Article 3.3.3.H.9.b or provide a copy of the notarized affidavit as required under UDC Article 3.3.3.H.9.a. This affidavit can be found at: https://www.tucsonaz.gov/files/pdsd/forms/C_of_O_Releif_Affidavit.pdf.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
09/28/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
10/19/2021 SBLOOD1 ENGINEERING REVIEW Passed