Permit Number: T21CM07155
Parcel: 11010019A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM07155
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2021 JPEELDA1 FIRE REVIEW Approved
09/14/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/15/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/15/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/15/2021 ROBERT SHERRY WATER REVIEW Completed
09/21/2021 STEVE SHIELDS ZONING REVIEW Approved
09/21/2021 SSHIELD1 ENGINEERING REVIEW Passed
09/21/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/29/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments and provide a written response,

The electrical requirements for the water heater shown on the electrical power plan does not correlate with the panel schedule.

The lighting branch circuit is not shown on the lighting plan or the panel schedule. Please clarify.

The line diagram calls the breaker panel ‘FMK’ and the floorplan and panel schedule call it ‘FHK’ . Please clarify.

REF; 2018 IBC 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements