Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM07134
Parcel: 106023040

Address:
3820 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM07134
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2021 ROBERT SHERRY WATER REVIEW Completed
10/27/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM07134

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Denied
5.Correction partially complied, but you need to be 10' from edge of roof or provide guards in an approved manner. Plans
show the roof hatch at 6'11" from edge of roof (IMC2018,304.11)

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved