Permit Number: T21CM07134
Parcel: 106023040

Address:
3820 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM07134
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM07134


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Denied
1. Provide smoke damper's where ducts serve the corridor and adjacent rooms(IMC2018,607.5.4)
2. Clarify where this exhaust duct is going(IMC2018,106.3.1)
3. Provide 140 CFM of exhaust air and provide approximately the same of supply air to men's and women's bathrooms (IMC2018,403.3.1.1)
5. Provide a permanent access to roof's, elevated 16' above grade in and approved manner (IMC2018,306.5)
6. It shall be noted that the duct smoke detectors shall be supervised by the building fire alarm system (IMC2018,606.4.1)

ELECTRICAL REVIEW COMMENTS
Conditionally Approved
EP-101: Should identify or provide note or for fused disconnect D1 next to CT meter cabinet for Electrical Contractor.
EP-602: Panel A 20 amp 2 pole CB# 65, 67 and #12 AWG feeds for water heater are undersized. Correct for construction.

PLUMBING REVIEW COMMENTS:
Denied
1). Include a detail showing how the gas piping will be attached to the roof. Add detail to P102 or P501. -IFGC 404.9 A106.3.1
2). Gas Equipment note 221613.00-11 on P501 states there are other gas appliances other than the rooftop units, this doesn't correlate with P-102 Gas piping plan. Update either incorrect page. --IFGC A106.3.1
3). Update P-102 or P101 with the gas pipe sizing table used. -IFGC 402.4
4). Update TMV location to include lavatories on the P601 plumbing fixture schedule. -IPC 419.5
5). On P601 Add the manufacture name & model number of the backflow devices to be used for the coffee maker & refrigerator. IPC A106.3.1 608.17.1.2
6). If the Backflow devices shown on P601 for the coffee maker & refrigerator have relief ports, illustrate where indirect discharge will terminate. -IPC 608.15.2.1
09/14/2021 JPEELDA1 FIRE REVIEW Approved
09/20/2021 STEVE SHIELDS ZONING REVIEW Approved
09/20/2021 SSHIELD1 ENGINEERING REVIEW Passed
09/20/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/28/2021 ROBERT SHERRY WATER REVIEW Reqs Change 1. Show the location of the proposed water meter, backflow preventer, and the water service pipe on a site plan. Provide the size of the water meter serving this building. Reference: Section 107.2.1 and 107.2.6, IBC 2018.
2. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water (e.g. not inside of the building). Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf

Final Status

Task End Date Reviewer's Name Type of Review Description
09/29/2021 VVERA1 OUT TO CUSTOMER Completed