Permit Number: T21CM07127
Parcel: 11707208A

Address:
756 S STONE AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM07127
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2021 JVINCEN1 FIRE REVIEW Approved
09/14/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/15/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
09/15/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2018 and C404.5, IECC 2018
09/15/2021 ROBERT SHERRY WATER REVIEW Completed
09/21/2021 STEVE SHIELDS ZONING REVIEW Approved
09/21/2021 SSHIELD1 ENGINEERING REVIEW Passed
09/21/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/29/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide power for the Booster pump shown on the plumbing plan.