Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM07041
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/20/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM07041 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Denied 1. The fire access doors on the east wall are required to have a fire protection rating of not less than three hours due the reduced open space per Section 507.2.1 #3. MECHANICAL REVIEW COMMENTS: Approval Pending 1. All corrections complied 2. Approved/Subject to field approval ELECTRICAL REVIEW COMMENTS Approval Pending E6.1 POWER ONE-LINE, DIAGRAMS, DETAILS AND ELEVATION: Detail #3 show an Undersized #6 GND to ground rod. Needs to be upsized per NEC table 250.66. ABQ RESPONSE: Detail has been corrected. Review Response: It is still shown as a #6 GND. Review and correct PLUMBING REVIEW COMMENTS: Denied 3). Now that the gas information has been added to Plan Pg. P1.1 The gas information needs to include the sizing table used along with the Bldg Entrance pressure. Also complete note #19 Stating what existing and or new gas appliances this rerouted gas line is feeding. IFGC 402.4, 402.7, 410, Chapter 6 3B). New Gas note #16 says pipe gas across underside of roof? that note doesn't correlate with notes #15 & #17.? If piping is to be ran across roof include a mounting detail. -IFGC A106.3.1, 404.9, 407.2 6). Added waste receptor for Evap discharge on plan pg. P1.2 doesn't match the system design on P1.1 or show the waste receptor location on P1.1. Pages need to corelate. IPC- 106.3.1 |
01/28/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM07041 2020 W Prince Rd – I-1 Warehouse Addition (2nd Review) TRANSMITTAL: January 28, 2022 This site is located in the I-1 zone (UDC 4.7.29). General Merchandise Sales/Commercial Storage are permitted use in this zone (Table 4.8-5). See Use Specific Standards 4.9.13.Q, 4.9.10.A and 4.9.13.Q. 1. Zoning has reviewed the building plan for compliance with development package, DP21-0219, and although it appears that the building plans match the DP until the DP is approved, the building plans cannot be approved. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. |
02/04/2022 | SBLOOD1 | ENGINEERING | REVIEW | Approved | |
02/17/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | NFPA 20, 2016 - 4.13.2.1 Except as provided in 4.13.2.1.1.1, fire pump rooms not directly accessible from the outside of the building shall be accessible through an enclosed passageway from an enclosed stairway or exterior exit. 4.13.2.1.2 The enclosed passageway shall have a fire-resistancerating of the fire pump. 4.13.5.2 The intensity of illumination in the pump room(s) shall be 3.0 ft-candles (32.3 Lux), unless otherwise specified by a requirement recognized by the authprity having jurisdiction. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 |