Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM07041
Parcel: 10610005D

Address:
2020 W PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM07041
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM07041

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide accurate information regarding Current Codes per International Building Code 2018. The information provided is incorrect since State has adopted latest Codes. The Structural Calculations and Drawing S0.1 references ASCE7-10. Make revisions and resubmit.
2. Provide Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1.
3. Submit documentation regarding implementation of Special Inspections and Testing program during construction to observe compliance with the Design Concepts and Specifications.
4. Provide schedule of special inspections as required in IBC Section 1705.
5. The Structural Calculations for Floor Slab at Rack Base Plat (Page 22) references IBC2015. Revise calculations and resubmit.
Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.
BUILDING REVIEW COMMENTS:
Denied
1. The fire access doors on the east wall are required to have a fire protection rating of not less than three hours due the reduced open space per Section 507.2.1 #3

MECHANICAL REVIEW COMMENTS:
Denied
1. provide ventilation air to office area 1st floor and mezzanine (IMC2018,403.3.1.1)
2. Provide ventilation calculation table (IMC2018,403.3.1.1)
3. Provide permanent access to to roof structures above 16' from grade in an approved manner (IMC2018,306.5)

ELECTRICAL REVIEW COMMENTS
Denied
ES1.1 ELECTRICAL SITE PLA: Fixture schedule symbols differ from site plan lighting.
E1.1 POWER AND SPECIAL SYSTEMS PLANS:
Detail 4 calls out for 6-30L receptacles. These are 250 Volt rated and the circuit is 480 Volts. Need to specify 480 Volt rated receptacles.
Cannot locate Note #2 on sheet.
E6.1 POWER ONE-LINE, DIAGRAMS, DETAILS AND ELEVATION:
Detail #1: Need to provide short circuit current available at ECB and call out adequate KAIC rating for ECB.
Detail #1: Need to provide fire pump size and determine if ECB and feeders are properly sized and also comply with NEC 695 for LRA short circuit protection and voltage drop of conductors when carrying LRA.
Detail #3 shows aluminum conductor to finished grade. Aluminum should not contact earth.
Detail #3 show an Undersized #6 GND to ground rod. Needs to be upsized per NEC table 250.66

PLUMBING REVIEW COMMENTS:
Denied
1). Add gutter & downspout sizes with calculations that derive from -IPC 1106.3 & 1106.6 Update plan pg. A1.3
2). Add type of water piping materials to be used to plan page A0.2 -IPC 605.4 A106.3.1
3). Plan pg. C1.0 notes #4 & #9, states gas piping to be relocated. Add gas piping illustrations to the plumbing pages. -IFGC A106.3.1
4). Floor drain vents on P1.2 can't horizontally offset until a point of 6" above the floor drain being vented. -IPC 905.4, 905.5
5). Sanitary drain system shown on P1.1 that receives discharge from the evaporators will need to be vented. -IPC 901.2.1
6). Add a evaporator drain connection detail to plan pg. P6.1 that shows an indirect connection to a trapped waste receptor. - IPC 802.1.5, 1002.1, A106.3.1
7). Evaporator water connections on P1.2 need backflow protection. -IPC 608.3
8). Lavatories on P6.1 schedule need mixing valves. -IPC 419.5
9). Notate the drainage fixture value of the discharge of the evaporators to show the 1.5" traps & line will meet the minimum drain size. -IPC 709.2, 709.4, 709.4.1 Update P1.1 or on the requested detail from review comment #6
09/16/2021 ROBERT SHERRY WATER REVIEW Completed
09/17/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM07041
2020 W Prince Rd – I-1
Warehouse Addition (1st Review)

TRANSMITTAL: September 17, 2021

This site is located in the I-1 zone (UDC 4.7.29). General Merchandise Sales/Commercial Storage are permitted use in this zone (Table 4.8-5). See Use Specific Standards 4.9.13.Q, 4.9.10.A and 4.9.13.Q.

1. Zoning has reviewed the building plan for compliance with development package, DP21-0219, and although it appears that the building plans match the DP a building height was not provided on the DP as required. Until the required information is provided on the DP and Zoning confirms that the information matches, and the DP is approved, the building plans cannot be approved.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
09/22/2021 JPEELDA1 FIRE REVIEW Reqs Change 1. The fire access doors on the east wall are required to have a fire protection rating of not less than three hours due the reduced open space per Section 507.2.1 #3
2. Owner shall provide TFD with a fire sprinkler annalysis report for the High-Piled storage from a Fire Protction Engineer.
3. High-Piled storage requires a permit to be obtained from TFD in conjunction with Building permit.
4. Plan shall include a fire pump room location if one is being added including location, electrical and mechanical for that room
Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucosnaz.gov
520-837-7033
10/18/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.
11/22/2021 LSHAMIS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/22/2021 VVERA1 OUT TO CUSTOMER Completed