Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM07031

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. The construction type is listed as Type V. Provide additional clarification on whether it is Type V-A or V-B construction.
2. Provide an existing floor plan along with any demolition being completed. Include the existing square footing as well.
3. Provide a brief narrative of the use of this space. What are the processes being used?
4. Provide manufacture specifications for the metal insulated panels.
5. Provide the all bracing details for the irrigation room walls.
6. Provide any and all necessary structural calculations for the metal insulated pane

MECHANICAL REVIEW COMMENTS:
Denied
1. Provide a more detailed mechanical equipment schedule that includes all highly detailed information to complete a full review.
2. Provide a mechanical comcheck

ELECTRICAL REVIEW COMMENTS
Denied
1. Provide a one line diagram
2. Provide an electrical comcheck.

PLUMBING REVIEW COMMENTS:
N/A
09/16/2021 SSHIELD1 ENGINEERING REVIEW Passed
09/16/2021 ROBERT SHERRY WATER REVIEW Completed
09/16/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM07031
3529 E Golf Links Rd – I-1
TI Second Grow Room, Marijuana Dispensary Off-Site Cultivation Location (1st Review)

TRANSMITTAL: September 16, 2021

This site is located in the I-1 zone (UDC 4.7.29). Marijuana Dispensary Off-Site Cultivation Location is a permitted use in this zone (Table 4.8-5). See Use Specific Standards 4.9.9.E.2 and 4.9.13.Q.

1. Per UDC Article 4.9.9.E.2.k Odor Mitigation is required. Clearly demonstrate that these requirements are met. Provide test data shows how well the ion generator eliminates odors.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
09/16/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/24/2021 JVINCEN1 FIRE REVIEW Reqs Change Plans indicate CO2 gas is on-site and most probably being used for gas enrichment. Indicate on plans if CO2 enrichment is being used.
-Provide all documentation per IFC 5307.4.1
-Indicate on plans if a gas detection system is installed. I do not see any permits for such system.
-Provide all mechanical information, approved mechanical permit, per IFC 5304.4.4