Permit Number: T21CM07026
Parcel: 132130840

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM07026
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2021 JVINCEN1 FIRE REVIEW Approved
09/02/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM07026

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. There are adopted and applicable codes and standards missing from the cover sheet. Provide a comprehensive list of the adopted and applicable codes and standards.
2. Provide the existing square footage of the tenant space.
3. Provide an updated thorough egress plan.

MECHANICAL REVIEW COMMENTS:
Denied
1. The individual station exhaust fans are required be a minimum of 50 cfm per station. The plans indicate the two stations are sharing a 50 cfm exhaust.

ELECTRICAL REVIEW COMMENTS
Denied
1. Provide a one line diagram.
2. Provide a comcheck for lighting.

PLUMBING REVIEW COMMENTS:
Approved
09/15/2021 STEVE SHIELDS ZONING REVIEW Approved
09/15/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/21/2021 ROBERT SHERRY WATER REVIEW Completed
10/08/2021 JGARCIA1 ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/08/2021 VVERA1 OUT TO CUSTOMER Completed