Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T21CM06963
Parcel: 129064910

Address:
2814 E 21ST ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM06963
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM06963
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:

1. Show the location and size of the electric line from property line to both buildings, R106.1.1. Identify if the electrical service requires an upgrade or replacement.

STRUCTURAL PLANS:

1. Provide a complete roof framing plan with beams and rafters sized with appropriate prescriptive load carrying capacity, R301.1 or provide an engineer’s sealed plan set for performance compliance consideration, R301.1.3. Update the plans with roof construction details of joist and fastener sizes showing 2018 IRC compliance or provide an engineer’s design.

SECTIONS - DETAILS:

1. Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” continuous reinforced footing depth below the undisturbed ground surface R403.1. Show exterior wood siding, sheathing and wall framing anchored with ½” x 10” bolts and with a 6” clearance above the ground, R317.1 item 5. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground, R317.1 item 5. This dimension is required in addition to the 4” weep screen clearance for a compliant foundation and floor height.

ELECTRICAL PLANS:

1. Notate the smoke alarm with a power source from the building wiring and equipped with battery backup, R314.
2. Provide a Riser Diagram with a single service panel and a sub-panel to the second building, E3607.
3. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3404.13 & E3706.2.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
03/08/2022 NMARTEL1 ZONING REVIEW Approved