Permit Number: T21CM06953
Parcel: 106041760

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM06953
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2021 JVINCEN1 FIRE REVIEW Approved
09/08/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM06953/APT BLDG & T21CM07030/DEMO & CLUBHOUSE

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. The allowable tabular sq. ft. provided for building 1 on the area increase calculations is incorrect. The max tabular allowable sq. ft. for an A-2 occupancy of type V-B construction and protected by a NFPA 13 system is 24,000 sq. ft. according to Table 506.2. Provide clarification and provide updated area increase calculations.
2. It is assumed that a 13R sprinkler system is being used to protect the apartment building and a NFPA 13 sprinkler system is protecting the new clubhouse. The notes are vague is what systems are protecting what spaces. Please clearly indicate what sprinkler systems types are protecting what spaces.
3. During the demolition phase it will be important to maintain all the fire lanes and fire access. Please coordinate with the Fire Marshal.
4. There are no egress plans provided. Provide thorough egress plans for both the apartment building and the clubhouse.
5. There are no occupant loads provided. Provide occupant load calculations for both the apartment and clubhouse.
MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved
09/13/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM06953 & T21CM07030
3332 N Los Altos Ave
Multifamily & Clubhouse (1st Review)

TRANSMITTAL: September 13, 2021
This site is located in the R-3 zone (UDC 4.7.12). Multi-family residential is a permitted use in this zone (Table 4.8-2). See Use Specific Standards 4.9.7.B.6.

1. The building plans have been reviewed for compliance with Development Package (DP) DP21-0212, and although it appears that the building plans match the DP, until the DP is approved Zoning cannot approved the building plans.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
09/13/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
09/16/2021 ROBERT SHERRY WATER REVIEW Completed
10/18/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Instructions:
1. Is this for a new or existing activity application? - Please select New Application.

2. Submission Type - Select Floodplain Use Permit.

3. Project Name - Enter a name for your project.

4. Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided.

5. Type of Permit - Select Commercial or Residential (Residential is for work on single family residences and duplexes.)

6. Complete the Applicant Info. (Note APA# is for applicants with an advance payment account. Leave blank is you do not have an APA account.

7. Complete the Contractor, Owner and Architect/Engineer sections as applicable.

8. Supporting Documentation Upload - Provide a complete cost estimate for the project. You may also provide additional documents you think will be helpful.

9. Sign the application and submit.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
10/19/2021 VVERA1 OUT TO CUSTOMER Completed