Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM06952
Parcel: 11446027E

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM06952
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Completed
11/01/2021 ROBERT SHERRY WATER REVIEW Reqs Change Comment not resolved, provide the requested information. [Initial comment: Show the location of the proposed water meter, backflow preventer, and the water service pipe on a site plan. Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1 and 107.2.6, IBC 2018.]