Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2021 IMONSHI1 ZONING REVIEW Approved
09/21/2021 SBLOOD1 ENGINEERING REVIEW Approved
09/23/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM06946
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the site plan.

Show the Pima County assigned street address 2851 N West Plaza Dr on the site plan, R319.

SITE PLAN:

1. Identify the utility lines requiring upgrade or replacement., R106.1.1. Minimum size for a pipe supplying two bathrooms within the building is 1”, P2903.7.

SECTIONS - DETAILS:

1. Show wood framing members resting on concrete as pressure treated, R317.1 item 2 and show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground, R317.1 item 5. Update detail #2/F1
2. A vented attic space requires a calculation for showing the attic ventilation opening size using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation. Account for the existing attic space if removing or blocking existing vents.

PLUMBING PLANS:

1. When specifying a gray drain line with a (drainage and waste listed) diverter valve, show a complete collection and discharge system consistent with P3009 for Recycling Systems with backflow and overflow provision.

ELECTRICAL PLANS:

1. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16.

If you have any questions, please contact: