Permit Number: T21CM06942
Parcel: 138060030

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM06942
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2021 LSHAMIS1 ZONING REVIEW Reqs Change CDRC Transmittal

FROM: Loran Shamis
PDSD Zoning Review Section

PROJECT: T21CM06942
SFR - carport enclosure (1st Review)
818 W Santa Maria St

TRANSMITTAL DATE: September 1, 2021

DUE DATE: September 10, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

The proposed use is single family residential (SFR), which is permitted in the R-1, subject to use specific standards 4.9.7.B.1-.9 and .11 (Table 4.8-2).

01. COMMENT: Provide a residential plot plan that meets the requirements found at https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf
This plan will:
Be drawn at an engineering scale, i.e. 1" = 10'
Provide a lot coverage calculation
Show the locations of all utilities
Indicate the zoning of the surrounding properties
Provide a legal description

For questions regarding Zoning comments, please contact me at: Loran.Shamis@tucsonaz.gov
To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp
09/17/2021 SBLOOD1 ENGINEERING REVIEW Passed
09/23/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM06942
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits

SITE PLAN:

1. Show the location and size of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. Identify the utility lines requiring upgrade or replacement. Minimum size for a pipe supplying two bathrooms within the building is 1”, P2903.7.

FLOOR PLANS:

1. Show the functional name of each proposed room and each adjacent room, R106.1.1. New bedrooms and removed windows from existing bedrooms must show code compliance for egress.
2. Show sleeping rooms with R310 compliant egress. The window shown at Exterior West elevation 2 on A-202 is undersized.

SECTIONS - DETAILS:

1. Show a complete cross-section detail of the new exterior wall, R106.1.1. Show wall and ceiling compliant insulation including at existing renovated walls. Show the minimum 12” reinforced footing depth below the undisturbed ground surface R403.1.
2. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground, R317.1 item 5. These dimensions are required in addition to the 4” weep screen clearance for a compliant foundation and floor height.
3. Show wood framing members resting on concrete as pressure treated, R317.1 item 2.
4. A vented attic space requires a calculation for showing the attic ventilation opening size using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation.

PLUMBING PLANS:

1. Provide a fixture unit schedule using 2018 code values for verifying the required pipe sizes, Table P2903.
2. Show horizontal branch drainpipes sized with acceptable number of fixture units, Table P3005.4.1. (max 6 units on 2” pipe size)
3. Show plumbing vents (VTR) within acceptable distances from traps, P3105.1. (1 ½”-6’, 2”-8’, 3”-12’).

ELECTRICAL PLANS:

1. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside in the immediate vicinity.
2. Interior alterations require the installation of smoke alarms at existing bedrooms, R314.2.1. Provide notation if the smoke alarms are existing or proposed.
3. Show Bathroom receptacles on a separate 20 AMP circuit (dedicated) with outlets at no other location, E3703.4 and E3901.6.
4. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review