Permit Number: T21CM06924
Parcel: Unknown

Address:
4152 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM06924
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2021 JVINCEN1 FIRE REVIEW Approved
09/07/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/09/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/09/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Specify that the metering faucet for the lavatory dispenses a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide tempered water for the public restroom lavatory using an approved device conforming to ASSE 1070 or a tankless water heater listed to ASSE 1084. Reference: Sections 416.5 and 607.1.2, IPC 2018.
09/09/2021 ROBERT SHERRY WATER REVIEW Completed
09/13/2021 STEVE SHIELDS ZONING REVIEW Approved
09/13/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/20/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/15/2021 SBLOOD1 ENGINEERING REVIEW Passed