Permit Number: T21CM06875
Parcel: Unknown

Address:
3835 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM06875
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2021 JVINCEN1 FIRE REVIEW Approved
09/08/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/13/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018.
2. If the lavatory is to have an independent vent, the drain from the lavatory must connect to the water closet drain, not the water closet vent. Reference: Section 901.4, IPC 2018.
09/13/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show how the clothes dryer installation complies with Section 504.6, IMC 2018 (make up air).
09/16/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/24/2021 DBENOIT1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/24/2021 DBENOIT1 APPROVAL SHELF Completed
09/24/2021 DBENOIT1 OUT TO CUSTOMER Completed
09/24/2021 DBENOIT1 REJECT SHELF Completed