Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM06875
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/02/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
09/08/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/13/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018. 2. If the lavatory is to have an independent vent, the drain from the lavatory must connect to the water closet drain, not the water closet vent. Reference: Section 901.4, IPC 2018. |
09/13/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Show how the clothes dryer installation complies with Section 504.6, IMC 2018 (make up air). |
09/16/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/24/2021 | DBENOIT1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/24/2021 | DBENOIT1 | APPROVAL SHELF | Completed |
09/24/2021 | DBENOIT1 | OUT TO CUSTOMER | Completed |
09/24/2021 | DBENOIT1 | REJECT SHELF | Completed |