Permit Number: T21CM06874
Parcel: 126134850

Address:
4659 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM06874
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM06874

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. Provide evidence that the rear exterior wall meeting the requirements of Table 602, due to the wall being close to the potential property line.

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved
09/09/2021 SSHIELD1 ENGINEERING REVIEW Passed
09/09/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/09/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM06874
4659 E 22nd St
Marijuana Facility - Dispensary – C-2

TRANSMITTAL: September 9, 2021

This site is located in the C-2 zone (UDC 4.7.21). Marijuana Facility - Dispensary is a permitted use in this zone (Table 4.8-4), subject to Use Specific Standard 4.9.9.E.1.

1. As you are proposing exterior work, addition of a generator, curbing and restriping, a Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites must be submitted and approved prior to approval of this building plan. The checklist can be found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf.
A DP is a separate submittal from the building permit and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using the “Submission Type”, “Site Review”.

2. Clearly demonstrate on the plans how the requirements of UDC Article 4.9.9.E.1.d & .l are met.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
09/16/2021 ROBERT SHERRY WATER REVIEW Reqs Change 1. Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.
2. Show the location of the water meter, backflow preventer, and the water service pipe on a site plan. Reference: Section 107.2.1 and 107.2.6, IBC 2018.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/16/2021 VVERA1 OUT TO CUSTOMER Completed