Permit Number: T21CM06813
Parcel: 113021080

Address:
1230 E ALLEN RD

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM06813
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM06813
1230 E Allen Rd
Separate two dwelling units (1st Review)

TRANSMITTAL DATE: September 1, 2021

This site is located in the R-2 zone (UDC 4.7.9). A single family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6, .9, & .10.

1. Provide approved permit documentation that show the two dwelling units on this site.

If you have any questions about this transmittal, please contact Elisa Hamblin at ElisaHamblin@tucsonaz.gov.
09/01/2021 SSHIELD1 ENGINEERING REVIEW Passed
09/20/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM06813

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes.

Provide a single set of plans in a .PDF file.

Sample drawings are shown as an example: https://www.tucsonaz.gov/pdsd/residential-permits

SITE PLAN:

Provide a site plan showing all buildings, R106.1.1. Show the location of utility lines to the building.

FLOOR PLAN:

Provide a floor plan showing the function of the enclosed patio. Show door locations and window sizes with type identified as XO or SH. Include the window opening size of adjacent bedroom where a door no longer opens to the exterior. This window requires egress compliance, R310.

SECTIONS - DETAILS:

1. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5) with minimum ½” diameter anchor bolt and treated sill plates, R602.10.8 & R403.1.6. This may require a concrete stem when the floor is less than 6” above grade.
2. Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” footing depth below the undisturbed ground surface R403.1.
3. Provide the placement of ceiling/roof insulation. This determines the need for attic ventilation or the need for an air-impermeable layer if insulation at the roof sheathing, R806.5.

MECHANICAL PLANS:

Provide equipment details showing code compliant components, locations and sizes for supplying conditioned air to the enclosed patio, R303.9.

ELECTRICAL PLANS:

Provide wiring details showing code compliant device locations and circuit sizes. Show circuit number and size with receptacles at all walls and lighting control at each doorway both interior and exterior. Receptacle, lighting and smoke detector circuits require arc-fault protection, E3404 & E3706.

INTERNATIONAL ENERGY CONSERVATION CODE:

Provide insulation details minimum (R-13 walls and R-38 ceiling) showing code compliant placement of materials and ratings, N1101. Windows require a solar heat gain of 0.25 or better, N1102.1.

OUTDOOR LIGHTING CODE

Provide any alterations with details showing compliant fixtures. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations or show proposed fixtures as Full Cut Off (night sky friendly).

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review