09/15/2021 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T21CM06812
Roof top Solar Panels (1st Review)
5953 S PIN OAK DR

TRANSMITTAL DATE: September 15, 2021



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments.


COMMENT: The Plan Set shows a line-side tap, Line taps require compliance with NEC 230.46 and maintain UL listing. Update the plans showing a tap enclosure with sufficient space for the tap device.


COMMENT: Residential will review the application on the next submittal






If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans