Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM06810
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/14/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The revised plan calls for a tankless water heater to serve the relocated lavatory but does not indicate which of the four specified water heaters is to be installed. In addition, the electrical plan does not show power being supplied to the proposed water heater. [Second comment: The enlarged plumbing plan does not appear to comply with the requirements of C404.6, IECC 2018 (i.e. no more the 24" from the hot water source to the hot water outlet at the lavatory, assuming a ½" hot water supply; 6" for a ¾" hot water supply). Provide a design to meet the requirements.] [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018.] |