Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM06810
Parcel: 13606002C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM06810
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/07/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Keynotes 5 and 6 still refer to the wrong plumbing fixtures. [Initial comment: Correct floor plan keynotes 5 and 6 on sheet A1to refer to the correct plumbing fixture. Reference: Section 107.2.1, IBC 2018.]
2. The enlarged plumbing plan does not appear to comply with the requirements of C404.6, IECC 2018 (i.e. no more the 24" from the hot water source to the hot water outlet at the lavatory, assuming a ½" hot water supply; 6" for a ¾" hot water supply). Provide a design to meet the requirements. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018.]