Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM06810
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/07/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 12/07/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Keynotes 5 and 6 still refer to the wrong plumbing fixtures. [Initial comment: Correct floor plan keynotes 5 and 6 on sheet A1to refer to the correct plumbing fixture. Reference: Section 107.2.1, IBC 2018.] 2. The enlarged plumbing plan does not appear to comply with the requirements of C404.6, IECC 2018 (i.e. no more the 24" from the hot water source to the hot water outlet at the lavatory, assuming a ½" hot water supply; 6" for a ¾" hot water supply). Provide a design to meet the requirements. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018.] |