Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM06810
Parcel: 13606002C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM06810
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2021 JPEELDA1 FIRE REVIEW Approved
08/31/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/07/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide information on the sequence of operation for the restroom exhaust fan to show that all the air supplied to the restroom will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018.
09/07/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Correct floor plan keynotes 5 and 6 on sheet A1to refer to the correct plumbing fixture. Reference: Section 107.2.1, IBC 2018.
2. Verify that the automatic faucet for the public lavatory will operate for at least 10-seconds. Reference: Section 606.4, ICC/ANSI A117.1-09.
3. Provide tempered water for the public restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.
4. Verify that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018.
09/07/2021 ROBERT SHERRY WATER REVIEW Completed
09/08/2021 STEVE SHIELDS ZONING REVIEW Approved
09/08/2021 SSHIELD1 ENGINEERING REVIEW Passed
09/08/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/15/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved