Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM06810
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/30/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
08/31/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/07/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide information on the sequence of operation for the restroom exhaust fan to show that all the air supplied to the restroom will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018. |
09/07/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Correct floor plan keynotes 5 and 6 on sheet A1to refer to the correct plumbing fixture. Reference: Section 107.2.1, IBC 2018. 2. Verify that the automatic faucet for the public lavatory will operate for at least 10-seconds. Reference: Section 606.4, ICC/ANSI A117.1-09. 3. Provide tempered water for the public restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018. 4. Verify that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018. |
09/07/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
09/08/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
09/08/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
09/08/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
09/15/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |