Permit Number: T21CM06795
Parcel: 117060640

Address:
219 N 3RD AV 141

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM06795
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response. It appears you are confusing this activity T21CMO6795 with T21CM06793. See review comments below for T21CM06793......
01-06-2022

1. The resubmittal of a site plan does not clarify the previous electrical review comment...The Panel ‘3A’ and meter for this space were cleared to TEP per the previous activity and permit # T20CM01037 REV 1, on 11-25-2020 by inspector Ernie Stevens. The older approved plans submitted for this activity T21CM06793 WITH THE REQUEST FOR A NEW METER does not make any sense since the submitted plans show older submittals prior to T20CM01037 REV 1. Please clarify.

My contact phone # is 520-909-5173 or email, Dan.santacruz@tucsonaz.gov if needed.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, 2012 Tucson/Pima County outdoor Lighting Code, (OLC).