Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM06795
Parcel: 117060640

Address:
219 N 3RD AV 141

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM06795
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change The applicant submitted an application for a electrical permit with the scope of work stated as, "New service meter" . Also submitted was a full set of plans for "Wiilow Salon Expansion" that was approved and stamp by City of Tucson PDSD in the year of 2021... The electrical plan shows all meters for the future suits accounted for. Please re-submit plans that show the correlation between the existing plans submitted and the New Meter installation for this application. Include any Sealed electrical plans needed to show the full scope of electrical work.
Ref; 2018 IBC 107.2.1, 2017 NEC,

Final Status

Task End Date Reviewer's Name Type of Review Description
09/15/2021 VVERA1 OUT TO CUSTOMER Completed