Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM06793
Parcel: 117060640

Address:
219 N 3RD AV 91

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM06793
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. The resubmittal of a site plan does not clarify the previous electrical review comment...The Panel ‘3A’ and meter for this space were cleared to TEP per the previous activity and permit # T20CM01037 REV 1, on 11-25-2020 by inspector Ernie Stevens. The older approved plans submitted for this activity T21CM06793 WITH THE REQUEST FOR A NEW METER does not make any sense since the submitted plans show older submittals prior to T20CM01037 REV 1. Please clarify.

My contact phone # is 520-909-5173 or email, Dan.santacruz@tucsonaz.gov if needed.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, 2012 Tucson/Pima County outdoor Lighting Code, (OLC).