Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T21CM06793
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/15/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | The applicant submitted an application for a electrical permit with the scope of work stated as, "New service meter in meter bank gear box" . Also submitted was a full set of plans for a Shell Improvement that was approved and stamp by City of Tucson PDSD in the year of 2020... The electrical plan shows all meters for the future suits accounted for. Please re-submit plans that show the correlation between the existing plans submitted and the New Meter installation for "Warehouse (91) this application. Include any Sealed electrical plans needed to show the full scope of electrical work. Ref; 2018 IBC 107.2.1, 2017 NEC, |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/15/2021 | VVERA1 | OUT TO CUSTOMER | Completed |