Permit Number: T21CM06786
Parcel: 11714146A

Address:
196 W SIMPSON ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM06786
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2021 JPEELDA1 FIRE REVIEW Approved
08/31/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/02/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide general room exhaust for any cooking appliance (e.g. convection oven) that does not require the installation of a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 2 and 507.3, IMC 2018.
09/02/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show the drainage fittings installed to guide sewage in the direction of flow (see the GCO at the inlet to the grease interceptor). Reference: Section 706.3, IPC 2018.
09/02/2021 ROBERT SHERRY WATER REVIEW Completed
09/08/2021 STEVE SHIELDS ZONING REVIEW Approved
09/08/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/27/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Instructions:
1. Is this for a new or existing activity application? - Please select New Application.

2. Submission Type - Select Floodplain Use Permit.

3. Project Name - Enter a name for your project.

4. Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided.

5. Type of Permit - Select Commercial or Residential (Residential is for work on single family residences and duplexes.)

6. Complete the Applicant Info. (Note APA# is for applicants with an advance payment account. Leave blank is you do not have an APA account.

7. Complete the Contractor, Owner and Architect/Engineer sections as applicable.

8. Supporting Documentation Upload - Provide a complete cost estimate for the project. You may also provide additional documents you think will be helpful.

9. Sign the application and submit.


Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
09/27/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments and provide a written response,

Theelectrical line diagram shows panel ‘L1’ as a 200 amp panel, the panel schedule shows panel ‘L1’ as 100 amp. Please clarify.

REF; 2018 IBC 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements