Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM06766
Parcel: 13705494G

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL

Permit Number - T21CM06766
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM06766
4800 S Landing Way – PAD-29
New Building - Food & Beverage Sales

TRANSMITTAL: September 8, 2021
This site is located in PAD-29, Food & Beverage Sales is an allowed use in the PAD,

1. The building plans have been reviewed for compliance with DP16-0044 and although for the most part it appears that the plan match, until the revision to DP16-0044 has been approved Zoning cannot approve the building plans.

2. Based on the site plan provided in the building plan set, sheet SD1.0, the proposed cart storage areas, called out under Keynote 19 will need to be accounted for on DP16-0044. Contact Cypress Civil (520) 499-2456 to coordinate these changes.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
09/08/2021 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
09/13/2021 ROBERT SHERRY WATER REVIEW Reqs Change Show the location of the proposed water meter, backflow preventer, and the water service pipe on the civil site plans noted on sheet P2.0. An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, etc.). Reference: Section 107.2.1 and 107.2.6, IBC 2018.
09/14/2021 JPEELDA1 FIRE REVIEW Reqs Change Fire Department Connection: IFC 2018, 912 Section 912.2.1. FDC shall be located on the front of the building.


Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
09/20/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
09/28/2021 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Completed
09/28/2021 STANTEC 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/28/2021 VVERA1 OUT TO CUSTOMER Completed