Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM06701
Parcel: 127081220

Address:
5457 E BURNS ST

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM06701
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2021 PCAMARE1 OIP REVIEW Reqs Change PROJECT: T21CM06701
Roof top Solar Panels (1st Review)
5457 E BURNS ST

TRANSMITTAL DATE: September 9, 2021



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments.


COMMENT: Show the sum of the main and backfeed breakers not exceeding 120% of the busbar (and conductor) rating, NEC 690.64 & 705.12 (D). Show the backfeed breaker incompliance with the bus limitation or increase the service panel rating.


COMMENT: Residential will review the application on the next submittal




If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
09/09/2021 NGARCIA3 OUT TO CUSTOMER Completed