Permit Number: T21CM06666
Parcel: 125073260

Address:
420 N OLSEN AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM06666
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2021 IMONSHI1 ZONING REVIEW Passed
09/14/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Instructions:
1. Is this for a new or existing activity application? - Please select New Application.

2. Submission Type - Select Floodplain Use Permit.

3. Project Name - Enter a name for your project.

4. Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided.

5. Type of Permit - Select Commercial or Residential (Residential is for work on single family residences and duplexes.)

6. Complete the Applicant Info. (Note APA# is for applicants with an advance payment account. Leave blank is you do not have an APA account.

7. Complete the Contractor, Owner and Architect/Engineer sections as applicable.

8. Supporting Documentation Upload - Provide a complete cost estimate for the project. You may also provide additional documents you think will be helpful.

9. Sign the application and submit.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
09/14/2021 IMONSHI1 NPPO REVIEW Passed
09/14/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments and provide a written response,

Provide electrical plans, design and calculations performed by an Arizona Registrant (Electrical) who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work.

Sub- Panels not allowed in closets, NEC 240.24.

Include the full scope of work, branch circuit and feeder extensions, existing location of the sub- panels, etc.

Provide a complete line diagram, load calculations, panel schedules, AIC ratings of equipment, all feeder, branch circuit conductor sizes and types, AFCI and GFI protection where applicable, complete compliance with the 2017 NEC.

REF; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements