Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2021 PCAMARE1 ENGINEERING REVIEW Passed
08/26/2021 IMONSHI1 ZONING REVIEW Approved
09/13/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM06641
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:

1. Indicate the location and size of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. Show the utility lines requiring upgrade or replacement.

STRUCTURAL PLANS:

1. Update the roof framing plan showing consistency with the site plan. Show the closet rafters as new with a bearing structure, R301.1.
2. Provide rafter sizes and spacing in compliance with Table R802.4. Update the carport rafters or show as manufactured trusses.

SECTIONS - DETAILS:

1. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5) with minimum ½” diameter anchor bolt and treated sill plates, R602.10.8 & R403.1.6. This may require a concrete stem when the floor is less than 6” above grade. Update Section B on A4.
2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF.

PLUMBING PLANS:

1. Show plumbing alterations, R106.1.1.
2. Provide the water pipe diameter between the meter and shut off valve in compliance with P2903.7. A minimum 1” service pipe is required for supplying water to more than 9.5 fixture units.
3. Show plumbing vents (VTR) within acceptable distances from traps, P3105.1. (1 ½”-6’, 2”-8’, 3”-12’).

MECHANICAL PLANS:

1. Show dryer vent size and location for venting to exterior, M1501.

ELECTRICAL PLANS:

1. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside in the immediate vicinity.
2. Show Bathroom receptacles on a separate 20 AMP circuit (dedicated) with outlets at no other location, E3703.4 and E3901.6.
3. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16.